Technical Attributes

General Information
Brand ETHERLINE®
Product type Ethernet cable
valid fieldbus or Ethernet system Ethernet, ETHERNET/IP
Copper index 60.000  kg/km
Copper index (lb) 403.183  lb
Weight 101 kg/km
Country of Origin
To be confirmed based on the actual goods supplied. Please contact us for confirmation before placing your order.
Electrical Characteristics
Maximum operating voltage (not for power transmission) 125
Nominal surge impedance 100
Segregation class according to EN 50174-2 D
Nominal voltage 50 V AC rms / DC according to (manufacturer specifications)
Supports Power over Ethernet IEEE 802.3af (PoE), IEEE 802.3at (PoE+), IEEE 802.3bt (4PPoE)
Loop resistance at 20°C 16.0
Possible data transmission rates 10000
Signal propagation speed (nom.) 0.79
Test voltage core/screening 1
Test voltage core/core 1
Product Design
Nominal core diameter 1.3
Conductor design solid conductor
Nominal outer diameter 7.2  mm
Conductor material Bare copper
Nominal conductor cross-section (metric) 0.25  mm²
Conductor number/size 2x(4x2x23/1AWG)
Shielded

Core identification Colours
Cable shape Separable twin
Number of pairs 8
Outer sheath colour yellow
Stranding type Twisted-pair
Pair shielding type Aluminium-laminated plastic foil
Leading conductor cross-section AWG
Shielding, short form S/FTP
With rodent protection

Conductor colour code PROFINET Colour code 4-pair
Type of overall screening Tin-plated copper braiding
Number of cores 16
Nominal conductor cross-section (AWG) 23 AWG
Core insulation basic material Polyethylene
Basic material of outer sheath Halogen-free compound
Including protective earth

Core insulation basic material, short form PE
With armouring

Cable sheath RAL colour RAL 1021
Number of wires 1
Basic material of outer sheath, short form LSZH
Product Characteristics
Flame-retardant

PWIS-free according to VDMA 24364-B2-L
Halogen-free according to IEC 60754-1
Temperature, occasionally moved min 0
Corrosiveness of combustion gases according to IEC 60754-2
Fast Connect (FC) cable

Temperature, fixed installation min -20
Temperature, fixed installation max 60
UV-resistant

Minimum bending radius in mm, fixed installation 28.8  mm
PWIS-free

Application area Fixed installation
max. conductor temperature, occasionally moved 0 °C to 50 °C max. conductor temperature
Oil-resistant

Ethernet cable category Cat.7A
Minimum bending radius in mm, occasionally flexing 57.6  mm
Minimum bending radius, stationary 4 x outer diameter
Minimum bending radius, occasionally flexing 8 x outer diameter
Temperature, fixed installation -20 °C to 60 °C max. conductor temperature
Flame retardance according to IEC 60332-1-2
Windable

Halogen-free

Temperature, occasionally moved max 50
Certifications and Standards
CE marking

VDE certified

Documentation
Notes
  • Photographs and graphics are not to scale and do not represent detailed images of the respective products.
  • Unless specified otherwise, the product values shown are rated values at room temperature. You can receive further values, such as tolerances, upon request if they are available and have been released for publication.
Product Family List
All articles from ETHERLINE® LAN 1000 Cat.7A
Article number Conductor number/size Cable shape Imp outer dia cable sheath nom Nominal outer diameter Flame retardance according to Copper index calc export Weight
2170614 4x2x23/1AWG Round 7.5 IEC 60332-3-24, IEC 60332-1-2 60 kg/km
2170971 4x2x23/1AWG Round 7.4 IEC 60332-3-24 56 kg/km
2170972 2x(4x2x23/1AWG) Separable twin 7.4 IEC 60332-3-24 113 kg/km
2170980 4x2x23/1AWG Round 7.2 IEC 60332-1-2 50 kg/km
2170981 2x(4x2x23/1AWG) Separable twin 7.2 IEC 60332-1-2 101 kg/km