Technical Attributes

General Information
Brand ETHERLINE®
Product type Ethernet cable
Copper index 24.000  kg/km
Copper index (lb) 161.280  lb
Weight 58 kg/km
Country of Origin
Germany. Note: The country of origin may vary depending on the actual goods supplied. Please contact us to confirm the country of origin for your order.
Electrical Characteristics
Maximum operating voltage (not for power transmission) 100
Nominal surge impedance 100
Segregation class according to EN 50174-2 D
Nominal voltage 48 V AC rms according to IEC
Supports Power over Ethernet IEEE 802.3af (PoE), IEEE 802.3at (PoE+), IEEE 802.3bt (4PPoE)
Loop resistance at 20°C 150
Possible data transmission rates 10000
Test voltage core/screening 1
Test voltage core/core 1
Rated voltage core to core 50 V AC rms according to IEC
Product Design
Nominal core diameter 1.3
Conductor design solid conductor
Nominal outer diameter 7.3  mm
Conductor material Bare copper
Min. outer diameter 7.1
Conductor number/size 4x2x23/1AWG
Shielded

Core identification Colours
Cable shape Round
Number of pairs 4
Outer sheath colour grey
Stranding type Twisted-pair
Pair shielding type Aluminium-laminated plastic foil
Leading conductor cross-section AWG
Shielding, short form S/FTP
With rodent protection

Type of overall screening Tin-plated copper braiding
Number of cores 8
Nominal conductor cross-section (AWG) 23 AWG
Core insulation basic material Polyethylene
Basic material of outer sheath Polyvinylchloride
Including protective earth

Core insulation basic material, short form PE
With armouring

Max. outer diameter 7.5
Cable sheath RAL colour RAL 7035
Number of wires 1
Basic material of outer sheath, short form PVC
Product Characteristics
Flame-retardant

PWIS-free according to VDMA 24364-B2-L
Temperature, occasionally moved min 0
Fast Connect (FC) cable

Temperature, fixed installation min -20
Temperature, fixed installation max 60
Installation temperature min. 0
UV-resistant

Minimum bending radius in mm, fixed installation 30.0  mm
PWIS-free

Application area Fixed installation
max. conductor temperature, occasionally moved 0 °C to 50 °C max. conductor temperature
Oil-resistant

Ethernet cable category Cat.6A
Minimum bending radius in mm, occasionally flexing 60.0  mm
Max. assembly temperature 50
Minimum bending radius, stationary 4 x outer diameter
Minimum bending radius, occasionally flexing 8 x outer diameter
Temperature, fixed installation -20 °C to 60 °C max. conductor temperature
Flame retardance according to IEC 60332-1-2
Windable

Halogen-free

Temperature, occasionally moved max 50
Certifications and Standards
CE marking

CPR fire class Eca
VDE certified

EAC certification number ЕАЭС N RU Д-DE.АЮ64.В.00130/20
EAC-certified

Documentation
Notes
  • Photographs and graphics are not to scale and do not represent detailed images of the respective products.
  • Unless specified otherwise, the product values shown are rated values at room temperature. You can receive further values, such as tolerances, upon request if they are available and have been released for publication.
Product Family List
All articles from ETHERLINE® LAN 500 Cat.6A
Article number Conductor number/size Imp outer dia cable sheath nom Nominal outer diameter Shielding, short form Halogen-free Copper index calc export Weight
2170143 4x2x23/1AWG 7.3 S/FTP No 58 kg/km
2170960 4x2x23/1AWG 7.3 S/FTP No 58 kg/km
2170961 4x2x23/1AWG 7.4 F/UTP No 60 kg/km
2170962 4x2x23/1AWG 7.3 F/FTP Yes 60 kg/km
2170963 4x2x23/1AWG 7.4 F/UTP Yes 60 kg/km